AO845A 3BSE045584R1 ABB High-density intelligent analog output module AC 800M System 800A
Product Overview
The ABB DI801 is a classic 16-channel digital input module in the AC 800M distributed control system, specifically designed for the highly reliable acquisition of discrete signals such as switch status, alarm signals, and equipment operation/fault feedback in industrial environments. This module supports 24V DC active or passive (dry contact) input, and features channel-level photoelectric isolation, reverse polarity protection and intelligent diagnostic functions. It is suitable for various automation scenarios such as power, water treatment, mechanical manufacturing and material conveying.
Core features
16 independent digital input channels
Input type: 24V DC (compatible with active signals or passive dry
contacts)
Input voltage range: 15-30 V DC (ON), < 5 V DC (OFF)
Input current: approximately 3.5 mA @ 24 V DC
High-reliability isolation design
Photoelectric isolation is achieved between the channel and the
backplane
Isolation voltage: ≥ 500 V AC (1 minute)
Surge resistance: ±4 kV (IEC 61000-4-5)
Intelligent diagnostic function
Real-time monitoring of the input signal status
Support channel-level open/short circuit detection (requires
coordination with external pull-up/pull-down circuits)
Fault information is simultaneously reported through the LED on the
front panel and the DCS alarm system
Technical parameters
Motor status monitoring: Collect operation/stop/fault signals (from
the auxiliary contacts of the contactor
Safety and interlock circuits: Status feedback for limit switches,
access control switches, and emergency stop circuits
Pump station and fan control: Signal input for liquid level switch,
pressure switch and flow switch
Material conveying system: photoelectric sensor, proximity switch,
encoder pulse counting
Energy management: Circuit breaker opening and closing positions,
transformer temperature control alarm
Installation and Usage instructions
Hardware installation
Insert DI801 into the S800 I/O electronic rack (such as TB840A);
Connect to the CI854A (optical fiber) or CI801 (electrical)
communication module via the ModuleBus cable;
For dry contact input, a 24V query power supply needs to be
provided either inside or outside the module (usually pulled up
from the system power supply through a resistor).
Software configuration
Create a DI801 device instance in Control Builder M;
Name each channel (such as "Pump1_Run_FB");
Optional "Filter time" can be enabled to suppress jitter (default:
1-10 ms);
Download the configuration to the AC 800M controller.
Debugging and verification
The green LED on the front panel indicates that the module is
operating normally.
Each channel corresponds to a status indicator (some versions have
channel leds or can be viewed through software).
The input status can be forced in Control Builder M for logical
testing.